t2

YQL series gas-fired thermal fluid heater

Product introduction

YQL series gas-fired thermal oil boilers have a three-pass round coil structure. A conical coil is used for the effective protection of the furnace wall at the boiler end. This product is equipped with an advanced combustion device and is fully automated in operation. After the burner ignites the fuel, flame fills the round coil tubes and transfers heat by radiation through the tube wall (first pass). The high temperature flue gas gathers at the back door and then turns to the convection tubes section (second pass), where heat transfer takes place by convection. The flue gas gradually cools down here and flows to the front door, where it is reversed and goes into the third pass. After that, it enters into the chimney through the economizer and is released into the atmosphere.


Product thermal capacity : 7000-29000 KW

Working pressure : 0.8-1.0 MPA

Digitized manufacture

The laying-off of steel tube adopts CNC 3D laser cutting machine.
The manufacture of square coil tube adopts CNC three-dimensional tube bending machine, no forced shaping .
The manufacture of serpentuator adopts serpentuator automatic production line, once-forming.

Full argon arc welding

Square coil tube and coil tube all adopt argon arc welding technique,which guarantees tubes are 100% qualified.

Long life span

The optimized radiation heating surface and convective heating surface, the medium flow is more reasonable, without overheat of the carrier and reduce the life;
Convection section: optimize convection heating surface and adopt effective fix and structural support to make its working life longer.
Set up effective flue gas partition for convection heating surface and cast partition to make it works longer.

Easy operation

We have combustion arch patent, which is available for different types of coals, even the anthracite is very easy to burn.
Flame-proof feeding bucket can avoid the feeding bucket is burnt and coking.
There is ash cleaning unit, which is easy for maintaining, operating and cleaning.

SPECIFICATIONS

ModelRated thermal power(KW)Rated thermal power(x10 4kcal/h)Design working temperature(≤℃)Rated working pressure(MPa)Thermal efficiency(≥%)System installation power(KW)
YQL-7000Q70006003200.890140
YQL-8200Q82007003200.890140
YQL-9400Q9400800320190200
YQL-10500Q10500900320190200
YQL-12000Q120001000320190240
YQL-14000Q140001200320190320
YQL-16500Q165001400320190380
YQL-18000Q180001600320190450
YQL-21000Q210001800320190520
YQL-23300Q233002000320190600
YQL-26000Q260002200320190700
YQL-29200Q292002500320190825
Top